CONTA-CLIP SMS-MULTI I/O User Manual

Page 26

Advertising
background image

SMS-MULTI-IO



- 25 -





5.4

5.4

5.4

5.4

Analog input

Analog input

Analog input

Analog inputssss

To use as a current input, lift the lid (see 3.1) and place a 250Ω / 0.1% resistor into the header on Ri:

To use as a voltage input the header must be empty.

5.4.1

5.4.1

5.4.1

5.4.1

Configuration

Configuration

Configuration

Configuration

Configure the following items with the software:

•

Name, this name must be unique and can not be used with any other input or output.

Default set as AI1 to AI8.

•

The input source:

•

0..10V

•

0..20mA

•

4..20mA

•

The unit for the input feedback. E.g. litres (Ltr) or kilograms (kg).

•

The min. value represents the scaled value for 0V, 0mA or 4mA.

•

The max. value represents the scaled value for 10V, 20mA.

•

Lower limit threshold.

•

Upper limit threshold.

•

Minimal change (hysteresis).

•

The Analog Inputs can generate messages with value and unit when:

•

The upper limit + hysteresis is reached

•

The lower limit – hysteresis is reached

•

The status recovers between the upper and lower limit +/- hysteresis


Note:

Note:

Note:

Note: The min./max. and threshold/hysteresis values are limited to 5 digits with a maximum of 2
decimals.

E.g.:

E.g.:

E.g.:

E.g.:
A water tank level is converted to 0..10V. 0V represents 10 litres and 10V represents 100 litres.
If a message should be sent

when the tank reaches a minimum of 20 litres and when during filling

the level of 80 litres is reached, configure the module as follows: