Extension pipe kit, Figure 1 – Toyotomi FF-V30T User Manual

Page 23

Advertising
background image

22

When using the “Extension pipe (L)” extension kit, the distance
between the heater exhaust pipe connection and the flue pipe
connection must be at least 1620 mm but no more than 2050 mm.
(See Figure 1 above.)
“Note that Exhaust Extension Kits L, M and S are designed for
installation inside the heated room, and for exposed (surface)
mounting only”.

No.

Name of Part

Q’ty

1

2

3

4

5

6

7

Adjustable Exhaust Pipe
Max. 1000 mm ~ Min. 570 mm

Exhaust Extension Pipe
(long, 1000 mm)

Intake Pipe (2000 mm)

Insulating Cloth Cover
(1000 mm)

Pipe Holder

Pipe Support Hardware

L-Shaped Exhaust Joint

1

1

1

2

2

3

sets

1

NOTE: Use “L”-shaped Exhaust Joint if necessary.

INSTALLATION WITH EXTENSION PIPE KIT (L)

Adjustable
Exhaust Pipe

Insulation
Cloth Cover

Exhaust Extension
Pipe (long)

Pipe
Holder

Intake Hose

Pipe Support
Hardware

(# 17187098)

(# 17212685)

(# 17206004)

(# 17206027)

(# 17206089)

(# 17206091)

(# 17206025)

Pipe Support Hardware

Pipe Holder (2 pcs.)

Pipe Holder Support (1 pc.)

Screw
(1 pc.)

Wood Screw

(2 pcs.)

Nut (1 pc.)

7

5

6

85 mm

90 mm

1

2

3

4

Max. 1000 mm

Max. 2000 mm

Max. 1000 mm

Max. 1000 mm ~ Min. 570 mm

Flue pipe
connection

Intake
Hose

Heater
Exhaust
pipe
connection

Figure 1

1620 ~ 2050 mm

EXTENSION PIPE KITS: L, M and S are designed to extend both Supply and Exhaust Pipes from the back of the
heater to the Flue Pipe which is the only approved method of transporting hot flue gasses through a wall. The
extension pipes must be installed “exposed surface mounted” within the heated room.

Extension Pipe Kit (L) PART #17206013

EXTENSION PIPE KIT

FF_V30T_Type B_US.qxd 14.6.2 11:51 ページ 22

Advertising