Cv-c relay expansion board wiring, Cvcwir1.cdr oe351, Cv- c controller relay expansion board – Auto-Zone Control Systems Auto-Zone CV-C Controller Installation Guide (Version 01A) User Manual

Page 6

Advertising
background image

Notes:

C

O

N

T

R

O

L

S

FILENAME

DATE:

B. CREWS

DESCRIPTION:

PAGE

DRAWN BY:

CV-C Relay Expansion Board Wiring

Line Voltage

Line Voltage

See Note 1

See Note 1

Required VA For Transformer

Each CV-C Controller = 20VA Max.

Required VA For Transformer

Relay Expansion Board = 20VA Max.

24VAC

24VAC

GND

GND

Caution!

Relay Expansion Board Must Have Address Switches Set As

Shown Or The Board Will Not Function.

Caution:

Disconnect The Modular Cable Between The CV-C Controller And The

Relay Expansion Board Before Removing Power From The Relay

Expansion Board. Reconnect Power And Then Reconnect The Modular

Cable Between The CV-C Controller And The Relay Expansion Board.

JOB NAME

1.)24 VAC Must Be Connected So

That All Ground Wires Remain

Common.

2.)All Wiring To Be In Accordance

With Local And National Electrical

Codes And Specifications.

07/08/99

CVCWIR1.CDR

OE351

1

Note:

Set-up, Programming And Monitoring Of The CV-C Controller Requires The

Use Of A Personal Computer And ZoneView AZ Software.

EXPANSION

SENSOR

PRESSURE

T'STAT

24VAC

GND

Relay Outputs R6 Thru R13 May Be User

Configured For The Following:

0 - Not Used (Nothing connected to this

output )

1 - Heating Stage

2 - Cooling Stage

3 - Humidifier Enable

4 - De-Humidifier Enable

5 - Scheduled Relay from Internal Schedule

6 - Scheduled Relay from External Schedule

(Only 1 Available!)

CV- C Controller

Relay Expansion Board

EXPANSION PORT

24VAC

IN

OUT

COM

Connect Expansion Board

to CV-C Controller

with Modular Cable

Not Used

POWER

U4

U5

U3

U1

RELAY 1

RELAY 2

RELAY 3

ADDRESS

RELAY 4

RELAY 5

RELAY 6

RELAY 7

RELAY 8

N.O.

CONT

ACTS

1-8

RELA

Y

COMMONS

9,10

Warning:

If One Transformer Is Used To Power The CV-C Controller And The

Relay Expansion Board, Polarity Must Be Strictly Observed. If The

Polarity Is Reversed, Serious Damage To Both Boards Will Result.

Advertising