Avalon Firestyles Chelan DV-1996 to 1999 User Manual
Page 11

S
TOVE
I
NSTALLATION
(C
ONT
.)
- For Qualified Installers Only!
P
AGE
11
Approved Venting Configurations with a Horizontal Termination
¥
A Minimum of 2' rise is required directly off of the heater
¥
If using a Snorkel Termination (14" or 36") add the snorkel height to the vertical height (snorkel
terminations are used primarily for basement installations).
¥
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.
5 feet
10 feet
0 feet
11' (max)
5 feet
10 feet
0 feet
5 feet
10 feet
12'(max)
5 feet
0 feet
0 feet
NOTE:
Horizontal sections require a 1/4" rise every 12" of travel.
10 feet
11' (max)
12'(max)
NOTE:
Restrictor positions
are based upon lab
tests. The ideal
restrictor position may
vary slightly,
especially when the
termination is near a
demarkation line.
Restrictor
Position # 5
NOTE:
A minimum 2' rise is required
directly off of the stove.
Restrictor
Position # 1