586

9424200996 Rev L

Firmware

Version and Date

Change

2.05.00, Oct-11

•

Added Output Override Alarms

•

Added 1A setting range for Full Load Amps and IEC Hot Curve
Current settings of 49TC element

•

Enhanced voltage settings resolution for 27, 59, and 81
elements

2.05.01, Jun-12

•

Improved target reporting

•

Corrected issue where bad data in log file could prevent correct
power-up of relay

2.06.00, Sep-12

•

Added 55 Power Factor protection element

•

Added unbalance current protection mode for the 50 and 51
elements

•

Added security logging

2.06.01, Nov-12

•

Maintenance release

2.06.02, Dec-12

•

Improved logic timers

•

Improved SEF pickups

•

Improved output override operation through the front panel

2.06.03, Mar-13

•

Improved 51 element operation

•

Improved port access timers

•

Added DNP data

2.06.04, Mar-13

•

Improved distance to fault measurements

2.07.00, Nov-13

•

Made alarms available in BESTlogicPlus

•

Expanded Target Reset logic point to operate from all target
reset requests

•

Added an option to Modbus to perform group saves to reduce
write times

•

Made Settings Group available in scrolling screens

•

Added Power Loss alarm

•

Eight additional 49RTD elements

•

Improved 60FL coordination when upstream breakers open

•

Improved tracking of failed login attempts with bad user names

•

Improved reporting of breaker operate time

•

Added logic nodes and made minor improvements to IEC 61850
protocol

2.08.00, Apr-14

•

Added 40Q protection

•

Added a Language Selection setting to choose language for the
front-panel display

•

Added Russian language option

•

Updated Time Dial range for IEC curves in the 51 element

•

Improved Frequency Out-of-Range alarm to indicate when any
source is out of range instead of when all sources are out of
range

•

Improved 60FL operation to prevent chance of nuisance alarm
during settings group change

•

Improved Modbus response to reads with incorrect ID

•

Changed clock priority setup to prevent user from accidentally
disabling internal real-time clock

2.08.01, May-14

•

Corrected placement of data on scrolling metering screens