Time pickup test – Basler Electric BE1-50/51B-121 User Manual

Page 48

Advertising
background image

5-4

BE1-50/51B-214/-215/-223/-225 Testing

9252000994 Rev P

Figure 5-6. Target Operational Test Setup, BE1-50/51B-223

NOTE

When testing TIME overcurrent functions, INST PICKUP settings of 00 will

affect the calibration of the TIME functions. TIME PICKUP settings of 00 also

affect INST functions.

Test Procedure, Models BE1-50/51B-214/-215/-223 (Five Ampere Sensing Input)

Perform preliminary setup:

Time Pickup Test

Connect test setup as shown in Figure 5-1 (BE1-50/51B-214), Figure 5-3 (BE1-50/51B-215), or

Figure 5-5 (BE1-50/51B-223).

Insure that SW3 switches are set: SW3-1 for the operating frequency, SW3-2 to OFF, SW3-3 to

ON and SW3-4 to ON.

Set TIME DIAL to 0.0.

Set CURVE to S

Set TIME PICKUP to 0.5.

Set INST PICKUP to 90.

Step 1. Slowly increase current to terminals 5 and 6. PICKUP LED should turn RED at a maximum input

current of 0.550 ampere.

Step 2. Decrease input current until PICKUP LED turns GREEN then OFF.
Step 3. Set TIME PICKUP to 2.2.
Step 4. Slowly increase current to terminals 5 and 6. PICKUP LED should change from GREEN to RED

at an input current of 2.131 to 2.269 amperes.

Step 5. Decrease input current until PICKUP LED turns OFF.


BE1-50/51B-223

6

5

10

1

TIME

INST

2

CURRENT

SOURCE

INPUT

STOP

TIMER

START

AMPS

TEST SET

P0061-21

9

R

AC or DC

Voltage

Source

(V)

1 A Target Current

R = V/1

Rwatts = 1*V