Air for combustion and ventilation, Continued, Determining fresh-air flow for heater location – Desa VP26T User Manual

Page 5

Advertising
background image

107887-01E

For more information, visit www.desatech.com

For more information, visit www.desatech.com

5

5

AIR FOR COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space:

Includes the room in which you will install heater plus any adjoining

rooms with doorless passageways or ventilation grills between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ___________ cu. ft. (volume of space)

Example:

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling

height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.

2.

Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example:

2560 cu. ft. (volume of space) x 20 = 51,200 (maximum

Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Gas fireplace logs

_____________ Btu/Hr

Other gas appliances* + _____________ Btu/Hr

Total = _____________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws com-
bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

_____________ Btu/Hr

Vent-free heater

+ _____________ Btu/Hr

Total

= _____________ Btu/Hr

WARNING: If the area in which the heater may be

operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight
construction, provide adequate combustion and ven-
tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec-
tion 5.3 or applicable local codes.

4.

Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:

A.

Rework worksheet, adding the space of an adjoining room. If the ex-
tra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air From
Inside Building
, page 6.

B.

Vent room directly to the outdoors. See Ventilation Air From Out-
doors
, page 6.

C.

Install a lower Btu/Hr heater, if lower Btu/Hr size makes room un-
confined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.

40,000

20,000

60,000

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow For Heater Location

Advertising