Technical data – BECKHOFF KL4112 User Manual

Page 5

Advertising
background image

Technical data

KL4112

5


Technical data





Technical data

KL4112

Number of outputs

2

Power supply

24 V DC via the Power contacts

Signal voltage

0 ... 20 mA

Load

< 500

Accuracy

< ± 0.1% (of the upper range value)

Resolution

15 bits, configurable 16 bits

Conversion time

app. 3.5 ms

Electrical isolation

500 Vrms (K-Bus / signal voltage)

Current consumption from K-Bus

60 mA typ.

Bit width in the process image

O: 2 x 16 bits data (2 x 8 bits control/status optional)

Configuration

no address or configuration setting

Weight approx.

80 g

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibration/shock resistance

conforms to IEC 68-2-6 / IEC 68-2-27

EMC resistance Burst / ESD

conforms to EN 50082 (ESD, Burst) / EN 50081

Installation position

any

Type of protection

IP20


Connection

RUN - LED1

+O1

Power
Contacts

Shield

RUN - LED2

+O2

+24 V

0 V

Shield

Top View

Contact Assembly

13

O1

+ +

S

14

O2

S

5

C

D

6

7

8

1

A
B

2

3

4

+ O1

+O2

+24V

0V

Shield

Advertising