Description of functions

6

KL4112


Description of functions

The analog output terminal KL4112 generates output signals within the
range from 0 – 20 mA. The output current is output by the terminal with up
to 16-bit resolution. The output current is electrically isolated from the ter-
minal bus level.

Input format of
process data

In the default setting, process data is entered in twos complement (integer
-1 corresponds to 0xFFFF).

Process data item (Hex/decimal)

Output value

0x0000 (0)

0 mA

0x3FFF (16383)

10 mA

0x7FFF (32767)

20 mA


LED Display

The two RUN LEDs indicate the operating state of the affiliated terminal
channel.

RUN LED:
On – normal operation
Off – watchdog-timer overflow has occurred. The green LEDs go off if no
process data is transferred by the bus coupler for 100 ms. The output out-
puts a current that is configurable by the user (see feature register).

Process data

The process data arriving from the bus coupler is output to the process as
follows.

X = Process data of the PLC
B_a,A_a = Manufacturer scaling (R17,R28)
B_h,A_h = Manufacturer scaling (R19,R20)
B_w,A_w = User scaling (R33,R34)
Y_dac = Output value to the DA converter

Neither user nor manufacturer scaling active:
Y_0 = B_a + A_a*X

(1.0)

Y_dac = X


Manufacturer scaling active:
Y_1 = B_h + A_h * Y_0 (1.1)
Y_dac=Y_1

User scaling active:
Y_2 = B_w + A_w * Y_0

(1.2)

Y_dac=Y_2

Manufacturer and user scaling active:
Y_1 = B_h + A_h * Y_0

(1.3)

Y_dac = B_w + A_w * Y_1

(1.4)


The straight-line equations are activated via R32.