2 product overview, 1 technical data – BECKHOFF KL5101-0000 User Manual

Page 5

Advertising
background image

Product overview

KL5101

3

2 Product overview

Signal - LEDs

Control - LEDs

Inputs A

Sensor
Supply

Inputs B

+ 24 V (2x)

Inputs C

0 V (2x)

Logic Inputs

Shield (1x)

Status Input

Top View

Contact Assembly

13

15

Ue

B

A

C

B

A

C

+

+

S

S

14

16

Uo

G1 G2

I1

5

C

D

6

7

8

1

A

B

2

3

4

Ue, Uo

+ 24 V

0 V

G 1, G 2

C, C

B, B

A, A

Status Input,Shield



2.1 Technical data

Technical data

KL5101-0000

KL5101-0012

Sensor connection

A, A(inv), B, B(inv), zero, zero(inv),
difference signal (RS 485); Status input

Sensor operating voltage

5 V DC

Sensor output current

0.5 A

Counter

16 bits binary

Cut off frequency

1 MHz (at 4 time evaluation)

Quadrature decoder

1-2-4 time evaluation

Zero pulse latch

16 bits

Commands

read, set, activate

Supply voltage

24 V DC (20 V ... 29 V)

Current consumption from power contacts

0.1 A (without sensor load current)

Bit width in the process image

I/O: 2 x 16 bits data, 1 x 8 bits control/status

Current consumption from K-Bus

25 mA

Weight approx..

85 g

Permissible ambient

temperature range

during operation

-25°C ... +60°C*

0°C ... +55°C

during storage

-40°C ... +85°C*

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC resistance Burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Installation position

any

Type of protection

IP20

Approvals

CE, cULus, ATEX

CE

*) extended temperature range, but only
0°C ... +55°C (according to cULus for Canada and USA)
0°C ... +55°C (according to ATEX, see special conditions)

Advertising