Example

Reading register 8 in the BK2000 with a Kl3022 and the end terminal.

If the following bytes are transferred from the controller to the terminal,

Byte0

Control

Byte1

Not used

Byte2

Data OUT, high byte

Byte3

Data OUT, low byte

0x88

0xXX

0xXX

0xXX


the terminal returns the following type designation (0x0BCE corresponds to
the unsigned integer 3022).

Byte0

Status

Byte1

Not used

Byte2

Data IN, high byte

Byte3

Data IN, low byte

0x88

0x00

0x0B

0xCE


A further example

Writing register 31 in the BK2000 with an intelligent terminal and the end
terminal.

If the following bytes (user code word) are transferred from the controller to
the terminal,

Byte0

Control

Byte1

Not used

Byte2

Data OUT, high byte

Byte3

Data OUT, low byte

0xDF

0xXX

0x12

0x35


the user code word is set and the terminal returns the register address with
the bit 7 for register access and the acknowledgement.

Byte0

Status

Byte1

Not used

Byte2

Data IN, high byte

Byte3

Data IN, low byte

0x9F

0x00

0x00

0x00




Data transfer, function

Process data

The KL5121 terminal occupies 6 bytes in the coupler’s input process image
and 6 bytes in the output process image. There are two logical channels:
data channel 0 and data channel 1.

Data channel 0

Data channel zero consists of the control byte 0, input data word 0, status
byte 0 and output data word 0. Enables for the output functions are
communicated through channel zero, and status information is read in.
Parameter data can also be accessed.

Controller output data

CT-0: control byte 0
D0-0, D1-0: the terminal’s input data word 0

Controller input data

ST-0: status byte 0
D0-0, D1-0: the terminal’s output data word 0

Control byte 0

Control byte 0 is only used for register access.

MSB

REG=0

Advertising