2 maintenance, 3 decommissioning, 1 cleaning – BECKHOFF AX5801 User Manual

Page 16: 1 disposal

Advertising
background image

Operation

14

AX5801

3.2 Maintenance

The TwinSAFE drive option cards are maintenance-free.

WARNING

Observe the specified environmental conditions!

Please ensure that the TwinSAFE option cards are only stored and operated under the
specified conditions (see technical data).

3.2.1 Cleaning

Protect the TwinSAFE Drive option cards against unacceptable soiling during operation and storage!

The TwinSAFE Drive option card may not be used any further if it has been exposed to impermissible
contamination!

WARNING

Have soiled components checked!

Cleaning of the TwinSAFE Drive option card by the user is not permitted!

Please send soiled terminals to the manufacturer for inspection and cleaning!

3.3 Decommissioning

DANGER

Serious risk of injury!

Disconnect the servo drive from the mains and system voltage before removing the
TwinSAFE drive option card!

Due to the DC link capacitors, there may still be a potentially lethal voltage on the DC
link contacts X02 even after disconnecting the servo drive from the mains supply. Wait
5 minutes after disconnection and measure the voltage on the DC link contacts DC+
and DC-. The device is safe once the voltage has fallen below 50 V.

3.3.1 Disposal

In order to dispose of the device, it must be removed and fully dismantled.

Metal parts can be sent for metal recycling.

Electronic parts such as disk drives and circuit boards must be disposed of in accordance with
national electronics scrap regulations.

Advertising