Identifier allocation default identifier, Broadcast objects, Peer-to-peer-objects – BECKHOFF FC5101 User Manual
Page 61

Eiserstraße 5 / D-33415 Verl / Telefon 05246/963-0 / Telefax 05246/963-149
61
Identifier Allocation
Default identifier
CANopen provides default identifiers for the most important communication objects, and these are derived from
the 7-bit node address (the node ID) and a 4-bit function code in accordance with the following scheme:
For broadcast objects the node ID is set to ”0”. This gives rise to the following default identifiers:
Broadcast objects
Object Function
Function
Code
Resuting COB ID hex /
dez
Object for Comm. Parameter /
mapping
NMT
Boot-Up
0
0x00 / 0
- / -
SYNC Synchronisation 1
0x80 / 128
0x1005 + 0x1006 / -
Peer-to-Peer-Objects
Object
Function
Function
Code
Resulting COB ID hex /
dez
Objekt für Comm. Parameter /
Mapping
Emergency Status / Error
1
0x81 - 0xFF/ 129 - 255
- / -
PDO1 (tx)
dig. inputs
11
0x181 - 0x1FF / 385 - 511 0x1800 / 0x1A00
PDO1 (rx)
digital outputs
100
0x201 - 0x27F/ 513-639
0x1400 / 0x1600
PDO2 (tx)
analog inputs
101
0x281 - 0x2FF/ 641-767
0x1801 / 0x1A01
PDO2 (rx)
analog outputs
110
0x301 - 0x37F/ 769-895
0x1401 / 0x1601
PDO3 (tx)
analog inputs*
111
0x381 - 0x3FF / 897 -
1023
0x1802 / 0x1A02
PDO3 (rx)
analog outputs*
1000
0x401 - 0x47F/ 1025 -
1151
0x1402 / 0x1602
PDO4 (tx)
analog inputs*
1001
0x481 - 0x4FF/ 1153 -
1279
0x1803 / 0x1A03
PDO4 (rx)
analog outputs*
1010
0x501 - 0x57F/ 1281 -
1407
0x1403 / 0x1603
SDO (tx)
Parameters
1011
0x581 - 0x5FF/ 1409-1535 - / -
SDO (rx)
Parameters
1100
0x601 - 0x67F/ 1537-1663 - / -
Guarding Life-/Node-
guarding,
Heartbeat,
Boot-Up mes-
sage
1110
0x701 - 0x77F/ 1793-1919 (0x100C, 0x100D, 0x100E,
0x1016, 0x1017)
* For historical reasons, the Beckhoff default mapping applies to PDOs 3 and 4 in Beckhoff I/O devices. In most
configurations, PDOs 3 and 4 contain data related to analog inputs and outputs, but there can also be "excess"
data from digital I/Os, or data from special terminals. Details may be found in the Bus Coupler documentation.
Up until version 3 of the CANopen specification, default identifiers were assigned to 2 PDOs at a time. The
Beckhoff Bus Couplers correspond to this issue of the specification. After version 4, default identifiers are pro-
vided for up to 4 PDOs.