BECKHOFF FC5101 User Manual

Page 79

Advertising
background image

Eiserstraße 5 / D-33415 Verl / Telefon 05246/963-0 / Telefax 05246/963-149

79

Device-ID: The ID that the system manager has assigned to the FC510x monitor channel must be entered
here:

Storing: The size of the ring buffer memory for the screen display (Display) and for that data output (File) can
be set here.

Display: A filter for the display output can be specified here.

Trigger: Trigger conditions that will stop the measurement can be specified here. It is possible, for instance, for
a specific otherwise unused output to be set when an error occurs, and to trigger off this bit in the output mod-
ule's RxPDO.

Post Trigger: This can be used to specify how many telegrams are still to be recorded after the trigger condi-
tion has occurred. The number of telegrams recorded prior to occurrence of the trigger condition is only re-
stricted by the specified buffer size.

Trigger and display filters function in such a way that only those bits for which the mask is set to 1
are considered when selecting the identifier (ID) or the data bytes (Data). These bits are then che-
cked for conformity with the values specified in Value. The default setting (mask ID = 0x7FF and
mask data = 0x00) is relevant if the identifier (ID) specified in Value is to be recognised, regardless
of the data. If an identifier (ID) larger than 0x7FF (e.g. 0x800, default) is entered, the filter or trigger
is disabled.

Example:

The recording is to be stopped after 250 telegrams, after bit 0 in the second data byte of a telegram with identi-

Advertising