62

6. Error Handling and Diagnosis

Beckhoff FC510x LED Description

LED Behavior

The red ERROR LED and the green RUN help to quickly diagnose the status of the card:

Error LED
(red)

Run LED
(green)

Description

off

off

TwinCAT has been stopped

off

on

All configured bus nodes are error free (Box State=0), TwinCAT Task or
Process is running.

off blinking

with

2 Hz

The Task, whose process data is linked to the card, is not running.
All configured bus nodes have been found and are error free (Box State=0)

blinking with
2Hz

on

At least one box state is unequal zero (e.g. node not found, wrong configura-
tion, node in error), TwinCAT Task is running

blinking with
2 Hz

off

At least one box state is unequal zero (e.g. node not found, wrong configura-
tion, node in error), TwinCAT Task is not running

on

off

TwinCAT is running, CAN Controller is "Bus OFF". Physical CAN problem.
Possible reasons: e.g. terminating resistor missing, bus too long, wrong baud
rate, node address configured twice, short circuit, wiring error.
Restart is necessary

blinking with
20Hz

blinking with
20Hz

Configuration Upload is under way

blinking with
20Hz

off

card is in STOP mode