Seer, Cooling performance with extended ratings, 2hp13 split system heat pump – Ducane (HVAC) 2HP13 User Manual
Page 6
2HP13 Split System Heat Pump
seer
13
A blower time delay is required to achieve ARI rating.
Which is part of these air handler and furnace controls.
Above information is for nominal CFM.
Outdoor
Model
Indoor Model
Indoor
Temp
DB/WB
˚F
Outdoor Temp - DB˚F
65
82
95
105
115
Piston or Field
Installed
TXV
Btuh
S/T
kW
Btuh
S/T
kW
Btuh
S/T
kW
Btuh
S/T
kW
Btuh
S/T
kW
2HP13**18P
RBCS2M18C
****P
85/72
20,700
0.65
1.23 19,800
.69
1.43 19,100
.72
1.51 18,300
.74
1.58 17,000
.75
1.64
80/67
19,400
0.67
1.19 18,500
.72
1.37 18,000
.74
1.44 17,100
.77
1.50 15,800
.77
1.55
75/63
18,100
0.69
1.16 17,200
.75
1.31 16,900
.76
1.37 15,900
.80
1.42 14,600
.79
1.47
75/57
16,900
1.00
1.17 16,500 1.00 1.34 16,000 1.00 1.41 15,200 1.00 1.47 14,100 1.00 1.52
2HP13**24P
RBCS2M24C
****P
85/72
27,400
0.65
1.80 26,100
.69
2.06 25,500
.72
2.17 24,200
.74
2.27 22,400
.75
2.35
80/67
25,800
0.67
1.73 24,600
.72
1.98 24,000
.74
2.08 22,800
.77
2.17 21,200
.77
2.24
75/63
24,200
0.70
1.65 23,100
.74
1.89 22,500
.76
1.99 21,400
.80
2.07 20,000
.80
2.14
75/57
22,400
1.00
1.69 21,900 1.00 1.94 21,400 1.00 2.04 20,300 1.00 2.12 18,900 1.00 2.20
2HP13**30P
RBCS2M30C
****P
85/72
32,000
0.68
2.20 30,500
.72
2.52 29,700
.75
2.65 28,200
.78
2.76 26,200
.78
2.86
80/67
30,100
0.70
2.12 28,700
.75
2.43 28,000
.77
2.55 26,600
.80
2.66 24,600
.81
2.75
75/63
28,200
0.72
2.05 26,900
.77
2.33 26,300
.79
2.45 25,000
.82
2.55 23,000
.83
2.64
75/57
26,200
1.00
2.08 25,500 1.00 2.38 24,900 1.00 2.50 23,700 1.00 2.60 21,900 1.00 2.69
2HP13**36P
RBCS2M36C
****P
85/72
39,900
0.65
2.75 38,100
.70
3.15 37,200
.72
3.31 35,300
.75
3.45 32,700
.75
3.57
80/67
37,600
0.67
2.65 35,900
.72
3.03 35,000
.74
3.18 33,300
.77
3.31 30,800
.77
3.42
75/63
35,300
0.70
2.56 33,700
.73
2.90 32,800
.76
3.05 31,300
.79
3.17 28,900
.80
3.28
75/57
32,700
1.00
2.60 32,000 1.00 2.97 31,200 1.00 3.12 29,600 1.00 3.24 27,400 1.00 3.36
2HP13*42P
RBCS2M42C
****P
85/72
45,600
0.66
3.20 43,500
.71
3.60 42,500
.73
3.77 40,300
.76
3.91 37,400
.76
4.03
80/67
43,000
0.68
3.12 41,000
.73
3.49 40,000
.75
3.64 38,000
.78
3.77 35,200
.78
3.88
75/63
40,400
0.71
3.04 38,500
.74
3.38 37,500
.77
3.51 35,700
.80
3.63 33,000
.81
3.73
75/57
37,400
1.00
3.06 36,500 1.00 3.42 35,600 1.00 3.57 33,800 1.00 3.69 31,300 1.00 3.80
2HP13*48P
RBCS2M48C
****P
85/72
51,400
0.66
3.56 49,000
.71
4.05 47,800
.73
4.25 45,400
.76
4.42 42,000
.76
4.57
80/67
48,400
0.68
3.43 46,100
.73
3.90 45,000
.75
4.09 42,700
.78
4.25 39,600
.78
4.39
75/63
45,400
0.71
3.31 43,200
.74
3.75 42,200
.77
3.93 40,000
.80
4.09 37,200
.81
4.22
75/57
42,100
1.00
3.37 41,000 1.00 3.82 40,100 1.00 4.01 38,000 1.00 4.17 35,200 1.00 4.31
2HP13*60P
RBCS2M60C
****P
85/72
63,300
0.65
4.41 60,400
.69
5.00 58,900
.71
5.24 56,000
.74
5.45 51,800
.74
5.63
80/67
59,600
0.67
4.23 59,900
.72
4.78 55,500
.74
5.01 52,700
.77
5.20 48,800
.77
5.37
75/63
55,900
0.70
4.05 53,400
.74
4.56 52,100
.77
4.78 49,400
.80
4.96 45,800
.81
5.11
75/57
51,900
1.00
4.14 50,600 1.00 4.69 49,400 1.00 4.91 46,900 1.00 5.10 43,400 1.00 5.26
Cooling Performance with Extended Ratings
** - B, L, BC, LC
* - B, L
Note: Extented data shown is actual for models listed
and typical for all AHRI matches.