6.3.8 Relay Output Configuring

Channels 7 and 8 are fixed as type

OUTPUT: Relay” as shown in Figure 31 which uses

Channel 8 as an example. Each channel provides a relay contact rated at 30 VAC/DC, 2A.
Each relay has a normally-open and a normally-closed set of contacts. The channel BACnet
type will be Binary Output. On this screen, you can adjust the following parameters.

Channel Name

You can name the channel using no more than 63 characters. This
will be the object name for this channel (followed by the channel
number). For example, “Relay Output-1”.

BACnet Unit Group

The Others default can be set to any option in the list.

BACnet Unit Value

The NO_UNITS default can be set to any option in the list. The
available options depend on the BACnet Unit Group you specify.

BACnet Description

You can enter any string using no more than 63 characters.

ACTUAL HIGH

The default value of 1 is unchangeable.

ACTUAL LOW

The default value of 0 is unchangeable.

SCALED HIGH

The default value of 1 is unchangeable.

SCALED LOW

The default value of 0 is unchangeable.

Initial Value (Scaled)

The Off default outputs 0, but you may set a 0 or a 1.