Power Installation

3.2 Grounding

Displays MUST be grounded according to

the provisions outlined in any applicable

local and national electrical codes and

according to the specifications in this

manual. Daktronics requires a resistance to

ground of 10 ohms or less.

The display system must be connected to an

earth-ground electrode installed at the

display, as shown in Figure 5. Proper

grounding is necessary for reliable

equipment operation and protects the

equipment from damaging electrical

disturbances and lightning. Refer to

Drawing B-329675 for more information on

grounding.

The display must be properly grounded, or

the warranty will be void.

Important points about grounding:

Follow local and national codes: The material of an earth-ground electrode differs

from region to region and from conditions present at the site. Consult any local and

national electrical codes that may apply.

Do NOT use the support structure as an earth-ground electrode: The support

structure is generally embedded in concrete. If embedded in earth, the steel is either

primed, or it corrodes, making it a poor ground.

Provide one grounding electrode for each sign structure: The grounding electrode is

typically at least one grounding rod for each sign structure. Other grounding

electrodes as described in any applicable local and national electrical codes may be

used.

Confirm that resistance to ground is 10 ohms or less: This is required by Daktronics

for proper display performance. If the resistance to ground is higher than 10 ohms, it

will be necessary to install additional grounding electrodes to reduce the resistance.

The grounding electrode must be connected to the ground wire inside the display.

Figure 5: Correct Grounding