There are two considerations for power installation: installation with ground and
neutral conductors provided, and installation with only a neutral conductor provided.
These two power installations differ slightly, as described in the following
paragraphs:

Electrical Installation

3-7

r

Installation with Ground and Neutral Conducto s Provided

For this type of installation, the power cable must contain an isolated earth-ground
conductor. Under this circumstance, do not connect neutral to ground at the
disconnect or at the display. This would violate electrical codes and void the
warranty. Use a disconnect so that all hot lines and neutral can be disconnected.
Refer to

Figure 20

below for installation details. The National Electrical Code

requires the use of a lockable power disconnect within sight of or at the sign.

Figure 20: Installation with Ground and Neutral Conductor Provided

Installation with Only a Neutral Conductor Provided

Installations where no grounding conductor is provided must comply with article
250-32 of the National Electrical Code. If the installation in question meets all of the
requirements of article 250-32, the following guidelines must be observed:

• Connect the grounding electrode cable at the local disconnect, never at the

sign panel board.

• A disconnect that opens all of the ungrounded phase conductors should be

used.

• The neutral and the ground conductors should be bonded in the sign panel

board.

Refer to

Figure 21

below for installation details.