Dataprobe Serial iBootBar User Manual
Page 14
 
 
 
Page
14
Serial iBootBar v111207e
Control Input Operation 
 
The eight control inputs can be used to operate the outlets. Shorting any of the inputs to ground will change the state of 
the outlet with the same number as the input. (Input 1 controls Outlet 1, Input 2 controls Outlet 2, etc.) 
 
Caution: Use only dry switch or relay closures, or open collector relay drivers to connect to the sBB inputs. If you have 
any doubts about proper connections, consult Dataprobe Technical support. 
 
 
The default control is Input Open = Outlet On, Input Grounded = Outlet Off. 
This can be changed using the 
set outlet <n> control.on <open/closed>
command.
 
Example: 
set outlet 3 control.on closed Causes
Outlet three to be Input Closed (to Ground) = Outlet On, Input Open = Outlet Off
get outlet 3 control.on
will check the current setting.