Serial Operation 
Command Line Interface 
The Command Line Interface provides complete setup of all function of the iBootBar. Some commands of the CLI require administrative rights. These are 
indicated in the table below. 
 
To access the sBB, connect to the serial port and type Enter, the user will be prompted for Username and Password. The default for both is 
admin
 
Outlet Commands 
Command
Description
Access
Fact Def
get outlets
Returns the status of ALL the outlets the user has rights to.
User
get outlet <1-8>
Returns the status of the designated outlet. The user must have 
rights to the selected outlet. 
User
set outlet <1-8> <on/off/cycle>
Sets the selected outlet to the selected state. The user must have 
rights to the selected outlet. 
User
set outlet <1-8> name <name>
Sets the name of the selected outlet of the selected iBootBar. 20 
characters max. 
Admin
Outlet <#>
get outlet <n> control.on
Gets or sets the state that the control input causes the 
corresponding outlet to turn On. 
Admin
Open
set outlet <n> control.on <open/closed>
get outlet <1-8> initial.state
Get or set the initial state of the selected outlet of the currently 
selected iBootBar. Initial state is the condition of the outlet when 
the iBootBar is powered up. This command will be ignored if 
external control is enabled with 
set external control enable
Admin
Last
set outlet <1-8> initial.state <on/off/last>