INSTALLING

Continued

INSTALLATION AND CLEARANCES (Vent-Free Operation Only)

Figure 4 - Minimum Clearance to Wall and Ceiling

WARNING

Maintain the minimum clearances. If you can, provide greater clear-
ances from floor, ceiling, and adjoining wall.

LOG SIZING REQUIREMENTS

Log

Minimum Firebox Size

Size

Height

Depth

Front Width

18"

17"

14"

20"

24"

17"

14"

26"

MINIMUM FIREPLACE CLEARANCE

TO COMBUSTIBLE MATERIALS

Log Size

Side Wall

Ceiling

18” and 24"

16"

42"

Carefully follow the instructions below. This will ensure safe installation into a
masonry, U.L. listed manufactured fireplace, or AGA design certified vent-free
firebox listed for use with these models.

Minimum Wall and Ceiling Clearances (see Figure 4)

A. Clearances from the side of the fireplace opening to any combustible wall

should not be less than 16 inches.

B. Clearances from the top of the fireplace opening to the ceiling should not be

less than 42 inches.

42"

16"

Left and Right

Sides