Pre-installation preparation, Drw fw – Desa O-T L (V)DVC36(B)(H) User Manual

Page 4

Advertising
background image

www.desatech.com

118197-01C

4

D

RW

FW

Figure 2 - Common Fireplace Locations

Flush with a wall

Through exterior wall
enclosed in a chase

Corner
installation

Figure 3 - Fireplace Bottom Dimensions

9" (36")

36

1

/

4

" (4")

41" (36")
48" (4")

• There must not be any obstruction such as

bushes, garden sheds, fences, decks or util-

ity buildings within 24" from the front of the

termination cap.

• Do not locate termination cap where excessive

snow or ice build up may occur. Be sure to

clear vent termination area after snow falls to

prevent accidental blockage of venting system.

When using snow blowers, do not direct snow

towards vent termination area.

PRE-INSTALLATION

PREPARATION

LOCATION AND SPACE
REqUIREMENTS

Determine the safest and most efficient location

for your DESA direct-vent fireplace. Make sure

that rafters and wall studs are not in the way of the

venting system. Choose a location where the heat

output is not affected by drafts, air conditioning

ducts, windows or doors. Figure 2 shows some

common locations. Be aware of all restrictions and

precautions before deciding the exact location for

your fireplace and termination cap.

When deciding the location of your fireplace,

follow these rules:

• Do not connect this fireplace venting to a chim-

ney flue serving a separate solid-fuel burning

fireplace or appliance.

• Due to high temperatures, do not locate this

fireplace in high traffic areas, windy or drafty

areas or near furniture or draperies.

• Proper clearances must be maintained.

• If your fireplace is to be installed directly on

carpeting, vinyl tile or any combustible mate-

rial other than wood, it must be installed on a

metal or wood panel extending the full width

and depth of the fireplace. See Figure 3.

• Your fireplace is designed to be used in zero

clearance installations. Wall or framing material

can be placed directly against any exterior sur-

face on the back, sides or top of your fireplace,

except where standoff spacers are integrally

attached. If standoff spacers are attached to your

fireplace, these spacers can be placed directly

against wall or framing material. See framing

details on page 5.

• If you plan on installing a television or enter-

tainment center recessed above your fireplace, it

is recommended that you maintain a minimum

18" above top of louver opening.

• When locating termination cap, it is important

to observe the minimum clearances shown in

Figure 7, page 8.

• If recessing into a wall, you can avoid extra

framing by positioning your fireplace against

an already existing framing member.

• Do not recess termination cap into a wall or

siding.

• You may paint the termination cap with 450ºF

heat-resistant paint to coordinate with the ex-

terior finish.

CLEARANCES

Minimum clearances to combustibles for the fire-

place are as follows:

*Back and sides

0"

Perpendicular walls

6"

Floor

0"

Ceiling to louver opening 42"

Front

36"

Top of Standoffs

0"

Vent

(See venting instructions for

specific venting clearances.)

Combustible material with a maximum thick-

ness of 5/8" may be flush with the top front of

fireplace.

* For back and sides of fireplace, do not pack

with insulation or other materials. Zero inch

clearance to combustible materials are for fram-

ing purpose only.

1

1

/

8

" (36")

3

1

/

4

" (4")