Fenix ELSR-M User Manual
Page 3
 
ELSR – N-20-2-AO and N-30-2-AO
• for the technological heating of pipes to a set temperature
• for the defrosting of trays
• for the heating of outside areas (only for placing into concrete)
 
Technical parameters: 
 
Supply voltage: 230 V 
Max. operating temperature: 65°C 
Max. temperature of covering layer: 80°C 
Min. installation temperature: -10°C 
Min. radius of bend: 20 mm 
 
A table of lengths and protection of self-regulating cables 
 
Starting temperature 
(°C) 
Circuit-breaker with 
characteristics C 
 (A) 
ELSR – N- 20 – 2- AO 
Max. length (m) 
ELSR – N- 30 – 2- AO 
Max. length (m) 
+10 °C
6
10 
16 
20 
25 
47 
93 
120 
150 
187 
29 
58 
84 
105 
131 
0 °C
6
10 
16 
20 
25 
40 
80 
94 
116 
146 
29 
58 
70 
87 
109
-10 °C
6
10 
16 
20 
25 
34 
68 
78 
96 
121
22 
44 
61 
76 
95 
-20 °C
6
10 
16 
20 
25 
30 
60 
77 
83 
104
20 
40 
52 
64 
80