Flowserve LN User Manual

Page 17

Advertising
background image

LN, LNE, LNH, LNV, LNEV, LNC and LNEC USER INSTRUCTIONS ENGLISH 71576423 11-09

Page 17 of 32

flowserve.com

These operations must be carried out by personnel
with approved qualifications.
liquid before starting continuous duty operation.

5.6 Starting the pump

a)

Ensure flushing and/or cooling/

heating liquid supplies are turned ON before
starting the pump.

b) CLOSE the outlet valve.
c) OPEN all inlet valves.
d) Prime the pump.

e)

Ensure all vent connections are closed

before starting.

f) Start motor and check outlet pressure.
g) If the pressure is satisfactory, slowly OPEN outlet

control valve.

h)

Do not run the pump with the

outlet valve closed for a period longer than 30
seconds.

i)

If NO pressure, or LOW pressure, STOP the
pump. Refer to section 7, Faults; causes and
remedies
, for fault diagnosis.

5.7 Running the pump


5.7.1 Venting the pump

Vent the pump to enable all trapped air to

escape taking due care with hot or hazardous liquids.

Under normal operating conditions, after the pump
has been fully primed and vented, it should be
unnecessary to re-vent the pump.

5.7.2 Pumps fitted with packed gland
If the pump has a packed gland there must be some
leakage from the gland. Gland nuts should initially be
finger-tight only. Leakage should take place soon
after the stuffing box is pressurized.

If no leakage takes place the packing will begin to
overheat. If overheating takes place the pump should
be stopped and allowed to cool before being re-
started. When the pump is re-started, check to
ensure leakage is taking place at the packed gland.

If hot liquids are being pumped it may be necessary
to slacken the gland nuts to achieve leakage.

The pump should be run for 30 minutes with steady
leakage and the gland nuts tightened by 10 degrees
at a time until leakage is reduced to an acceptable
level, normally a minimum of 120 drops per minute is
required. Bedding in of the packing may take another
30 minutes.

Care must be taken when adjusting the gland

on an operating pump. Safety gloves are essential.
Loose clothing must not be worn to avoid being
caught up by the pump shaft. Shaft guards must be
replaced after the gland adjustment is complete.

Never run gland packing dry, even for

a short time.

5.7.3 Pumps fitted with mechanical seal
Mechanical seals require no adjustment. Any slight
initial leakage will stop when the seal is run in.

Before pumping dirty liquids it is advisable, if
possible, to run in the pump mechanical seal using
clean liquid to safeguard the seal face.

External flush or quench should be

started before the pump is run and allowed to flow for
a period after the pump has stopped.

Never run a mechanical seal dry, even

for a short time.

5.7.4 Bearings

If the pumps are working in a potentially

explosive atmosphere, temperature or vibration
monitoring at the bearings is recommended.
If bearing temperatures are to be monitored it is
essential that a benchmark temperature is recorded
at the commissioning stage and after the bearing
temperature has stabilized.

Record the bearing temperature (t) and the
ambient temperature (ta)

Estimate the likely maximum ambient
temperature (tb)

Set the alarm at (t+tb-ta+5)

°

C [(t+tb-ta+10)

°

F]

and the trip at 100

°

C (212

°

F) for oil lubrication

and 105

°

C (220

°

F) for grease lubrication

It is important, particularly with grease lubrication, to
keep a check on bearing temperatures. After start up
the temperature rise should be gradual, reaching a
maximum after approximately 1.5 to 2 hours. This
temperature rise should then remain constant or
marginally reduce with time. (Refer to section 6.2.3.1
for further information.)

Advertising
This manual is related to the following products: