Flowserve Tandem Seal User Manual

Page 6

Advertising
background image

6

Recommended Piping for Tandem Designs

Figure 3

API Plan 52

1. Solenoid valve in drain is normally open allowing primary seal weep age to

vent through orifice.

2. If primary seal leakage becomes excessive, the pressure switch in the

secondary seal thermal convection loop will activate alarm and close

solenoid valve in the drain line.

3. Bypass line around solenoid valve is normally closed but is used to bleed

system pressure.

Pressure Alarm

and Switch

Fill Connection

Supply Tank Assembly

API Plan 11

Bypass Line From

Pump Discharge

Orifice

.031" (.8mm)

Solenoid Valve

(normally open)

1 foot

(300 mm)

minimum

Bypass Valve

(normally closed)

To Recovery

Orifice

Option

Primary

Seal

Secondary

Seal