Adjusting the Minimum Pressure

Cutoff Feature on Old Transducers

Older models of the NT 3000 Transducer have a “Minimum Pressure
Cutoff” feature. This allows the user to set a trip-point to activate when
the input signal falls below a certain point. This results in the pressure
output falling rapidly to approximately 2.0 psi, causing the valve to
close on an air-to-open valve. This feature is generally used when the
service requires a tight shutoff or to prevent throttling near the valve
seat. To adjust this feature, refer to Figure 12 and perform the following
steps:

NOTE: The zero and span settings of both the positioner and NT 3000
transducer should be verified to be accurate before the minimum
pressure cutoff feature is enabled and adjusted. Instructions for setting
the zero and span settings are described in the calibration section on
Page 4.

NOTE: Complete the following steps only when using the minimum
pressure cutoff feature.

1. Connect the NT 3000 transducer to the 30 to 150 psi air supply

pressure.

2. Remove the NT 3000 transducer housing cover.

c

WARNING: Disconnect I/P module power before removing
housing cover in explosive atmospheres; otherwise personal
injury may occur.

3. Connect an adjustable current source to the terminal block on the

circuit board. Apply the desired input signal to the positioner at

which the output pressure is to fall to approximately 2.0 psi. This
signal can range from the factory setting of 3.7 to
8 mA. See Figure 11.

4. Turn the minimum pressure cutoff pot clockwise until the output

pressure drops off.

5. Fine-tune the pressure drop-off point by increasing the input signal

and then decreasing it through the desired shut off signal. Observe
the signal value at which the pressure drops off. If the pressure
drops off at a lower mA signal than desired, turn the MPC pot
slightly clockwise. If the pressure drops off at a higher signal than
desired, turn the MPC pot slightly counterclockwise.

6. Repeat step 5 until the pressure drops off at the desired input

signal.

7. To disable the MPC feature turn the minimum pressure cutoff pot

(marked “MPC”) 20 turns counterclockwise or until it makes a
clicking noise.

Figure 11 – I/P Minimum Pressure Cutoff Adjustment Range

��

��

��

��

��

�������������������

���

��

��

��

���

��

��

��

��

��

��

�������

�������

�������

�������

����������������

Figure 12 – Old Style NT 3000 Transducer Circuit Board (housing cover removed)

���������������

��������

�����

������������

���������������

������������

���������������

��������������

�������

��������

������

����������

����

����������

����

����������