Reversing position transmitter signal, Table iv: specifications – Flowserve Valtek Position Pac User Manual

Page 6

Advertising
background image

29-6

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

Figure 6: Wiring Diagram

Figure 7: Power Supply Requirements

9b. Set the ZERO and SPAN potentiometers to their

approximate middle position. This is accomplished
by first turning each potentiometer clockwise 25
turns or until a ‘click’ is either felt or heard. Then turn
each potentiometer counterclockwise approxi-
mately 12 complete turns. Repeat steps 2 through 8
to complete calibration.

10. Replace the housing cover.

REVERSING POSITION TRANSMITTER
SIGNAL

The following instructions should be used when the sig-
nal being transmitted from the position transmitter is
either incorrect or needs to be reversed. Refer to
Figure 5.

1500

1250

1000

750

500

250

0

0 10 20 30 40 50 60

Max. Load Resistance, R (

)

L

Power Supply Voltage, V (volts)

PS

Operating

Region

R = V - 12.5V
20 mA

L max PS

Table IV: Specifications

Analog Output

Power Supply Range

12.5 to 40 VDC (24V DC typical)

Maximum Load

Maximum Resistance (ohms) =

Resistance

Supply Voltage - 12.5

(see Figure 3)

0.02

Current Signal Output 4-20 mA

Span

Adjustable from 5

°

to 100

°

of angular

rotation

Null

4 mA position may be set at any angular
position

Linearity

±

1.0% full-scale*

Repeatability

±

0.25% full-scale

Hysteresis

±

1.0% full-scale

Operating

-40

O

to 185

O

F (-40

O

to 85

O

C)

Temperature Range

Ambient Temperature For a 100

O

F (38

O

C) change in ambient

Range

temperature, maximum zero shift is

±

0.4% full scale, maximum span

shift is

±

0.7% full scale

Power Supply

Output signal changes less than
0.05% when supply voltage is varied
between 12.5 and 40 volts dc

Limit Switches

(SPDT)

20 amps, 125, 250, 480 VAC, ind. and

UL/CSA Rating (L23)

res. 1 Hp. 125 VAC; 2 Hp, 250 VAC, 0.5
amp. 125 VDC; 0.25 amp, 250 VDC res.

Mechanical

Input motion

±

105

O

from the center; spring

loaded to return to the center

* Linearity is

±

1.0% for 90

O

rotary shaft input. When mounted to

linear travel valves, linearity is dependent on linkage design and
stroke length. Typical linearity is

±

1.5% full-scale on Valtek Mark

One control valves.

NOTE: Instructions within parenthesis ( ) refer to older
Position Pac models characterized by a white label.

1. Remove the housing cover.

WARNING: On explosion-proof installations,
disconnect electrical power or be certain the
area is safe from combustible atmospheres be-
fore removing the housing cover.

2. Locate the switch next to the position transmitter’s

wiring terminal. Move switch to the opposite posi-
tion, CCW or CW (DIR or REV). Repeat steps 3-9 in
the

Calibration section for the position transmitter.

NOTE: The SPAN potentiometer will generally not
need readjustment.

3. Replace the housing cover.