Eters, Advance diagnostics, Artial – Flowserve 520MD Positioners User Manual

Page 6: Troke, Calibration, Ctuator, Riction, Nalog, Utput, Nput

Advertising
background image

DD User Manual - Logix® 520MD+ Series Digital Positioner FCD-LGENSF0017-00 8/13

© Flowserve Corporation

6


2.4.2

Max Lifetime

Maximum temperature reached since startup.

2.4.3

Min Lifetime

Minimum temperature reached since startup.

2.4.4

Max Reset

Maximum temperature reached since last reset.

2.4.5

Min Reset

Minimum temperature reached since last reset.

2.4.6

Max Power Up

Maximum temperature reached since last power up.

2.4.7

Min Power Up

Minimum temperature reached since last power up.

2.5

Hour Meters

Displays hours of operation.

2.5.1

Lifetime

Number of hours positioner has been in operation.

2.5.2

Reset

Number of hours positioner has been in operation since last
reset.

2.5.3

Power Up

Number of hours positioner has been powered up.

3

ADVANCE DIAGNOSTICS

Allows access to Partial Stroke Test

CAUTION: Starting the Partial Stroke Test will cause

closure member movement. Please, follow all safety
procedures.

3.1

Partial Stroke Test

Parameters needed to run a partial Stroke Test and see
results.

3.1.1

Start Partial Stroke Test

Starts the partial stroke test.

3.1.2

Pst Time Breakaway

Measured when the valve has moved ½ % from the starting
position.

3.1.3

Pst Pressure Difference

The pressure at the breakaway point.

3.1.4

Pst Time to Target

Actual time it took for the valve to arrive within 2% of the final
value.

3.1.5

Pst Time Limit

Time used for pass fail criteria for the partial stroke.

3.1.6

Pst Result

Pass/Fail indication of the test based on the reference time to
target and the actual time to target.

4

CALIBRATION

Gives access to Actuator/Stroke/Friction Calibration, Stroke
Calibration, Analog Output Calibration, and Analog Input
Calibration functions.

4.1

Actuator/Stroke/Friction

Combined calibration that calibrates the internal pressure
sensors of the positioner, the travel of the valve position
(zero and span), and if auto tuning is enabled the gain values
for the positioner are also calculated. Finally, a short
sequence of movements allows the positioner to update a
friction value for the valve assembly. Once set the friction
value will continue to update on its own during normal
operation.


4.2

Stroke

Combined calibration that calibrates the travel of the valve
position (zero and span) and, if auto tuning is enabled, the
gain values for the positioner are also calculated.


4.3

Analog Output

The Analog output calibration is only available for positioners
that have been supplied with the analog output module
installed in the positioner. The Analog output is updated to
match the stroke calibration of the positioner automatically
every time a stroke calibration is done. This calibration is
required if the 4-20 mA signal from the positioner needs to be
spanned to something other than 4-20 mA. This option is
also used to reverse the output if needed. Once setup
properly, this calibration is usually not required for ongoing
maintenance.


4.4

Analog Input

The Analog input calibration is updated to match the stroke
calibration of the positioner automatically every time a stroke
calibration is done. This calibration is required if the 4-20
mA signal to the positioner needs to be spanned to
something other than 4-20 mA. Once setup properly this
calibration is usually not required for ongoing maintenance.