Quick-check, Table 1: flange bolting torques, Installation – Flowserve Valtek Valdisk Control Valves User Manual

Page 2

Advertising
background image

10-2

WARNING: Keep hands, hair, clothing, etc. away from

the rotating disc and the seat when operating the valve.

Failure to do so could cause serious injury.

CAUTION: Because of Valdiskís self-centering seat,

there is no reason to open the valve at any time during

installation. Therefore, the valve should remain closed

until the valve is fully installed.

4. Connect air supply and instrument signal. Throttling valves

are usually equipped with valve positioners. Two connec-

tions are marked for the air supply and for the instrument

signal. Both cylinder and positioner are suitable for 150

psi air supply. An air regulator is not required unless the

supply pressure exceeds 150 psi. An air filter is recom-

mended unless the supply air is unusually clean and dry.

All connections must be free of leaks.

CAUTION: On valves equipped with air filters, the air

filter bowl must point down; otherwise, the air filter will

not perform properly.

NOTE:
5. Make sure proper clearance exists internally in the mating

piping to permit proper disc rotation.

6. Apply recommended torque values to line flange bolting

for proper sealing (see Table 1).

Quick-check

Prior to start-up, check the control valve by following these

steps:
1. Check for full stroke by making the appropriate in-strument

signal change. Observe disc position indicator plate

mounted on the transfer case. The disc should change

position in a smooth, rotary fashion.

2. Check all air connections for leaks. Tighten or replace any

leaky lines.

3. Evenly tighten the packing nuts to slightly over finger-

tight.

CAUTION: Do not overtighten packing. This can cause

excessive packing wear and high shaft friction, which

may impede shaft rotation.

After the valve has been in operation for a short time,

check the packing nuts to make sure they are just over

finger-tight (readjust if necessary). If packing box leak-

ing occurs, tighten the packing nuts only enough to stop

leakage.

4. To observe the valve failure mode in case of air failure,

position the valve to mid-stroke and shut off the air supply

or disconnect the instrument signal. By observing the

indicator plate, the disc should either fail open or closed.

If incorrect, refer to the ìReversing the Actuatorî section

in the appropriate Actuator Maintenance Instructions.

Table 1: Flange Bolting Torques

Valve Size

(Inches)

Rating

Torque

Carbon Steel

(ft-lbs)

Torque

Stainless Steel

(ft-lbs)

2

150
300
600

118
118
118

74
74
74

3

150
300
600

118
209
209

74

131
131

4

150
300
600

118
209
337

74

131
211

6

150
300
600

209
209
505

131
131
316

8

150
300
600

209
337
728

131
211
455

10

150
300

337
505

211
316

12

150
300

337
728

211
455

14

150

505

316

16

150

505

316

18

150

728

455

20

150

728

455

24

150

1009

631

30

150

1009

631

*Note: All values are + or - 10%

Installation

1. Before installing the valve, clean the line of dirt, scale,

welding chips, and other foreign material. Clean the gasket

surfaces thoroughly to insure leak-proof joints.

2. Check flow direction to be sure valve is installed correctly.

Fail-closed valves should be installed with the shaft up-

stream only on gas service. It is preferred that liquid

service valves must be installed with the shaft downstream

regardless of air failure action. However, under certain

flow conditions the valve can flow shaft upstream. Con-

sult factory if the valve must be mounted with the shaft

upstream in liquid service. Fail-open valves should be

installed with the shaft downstream.

WARNING: When installing the valve in-line between

flanges, make certain the flange face gasket covers

both seat retainer and body and surface. Failure to do

so will cause excessive leakage downstream. Refer to

ìSeat Insert/Snap-ring Configurationî in Figure 1.

3. Fully close the valve before and during the installation

process.

Advertising