• To avoid overloading the mechanical components, the recommended
permitted
relative differential pressures are:
DN 15 – 50 max.
24 bar
DN 65 – 100 max.
20 bar
DN 150 – 200 max.
15 bar
Recommended installation for
pressure-reducing valves
Medium temperature
< 100 °C
Installation distance from valve
10 x DN
(at least 1m)
Pressure-reducing
valve
Dirt trap (0.1 mm)
Medium
Medium
Rundown tank
Recommended installation for
pressure-reducing valves
Medium temperature
> 100 °C
Installation distance from valve
10 x DN
(at least 1m)
Dirt trap (0.1 mm)
Medium
Medium
Rundown tank
Relief valve
Recommended installation for
relief valves
Medium temperature
< 100 °C
Recommended installation for
relief valves
Medium temperature
> 100 °C