Limitorque MX Electronic Actuator FCD LMENIM2350-01 – 9/13

flowserve.com

FLOWSERVE PROPRIETARY INFORMATION

Use or disclosure of this information is subject to the restrictions on the title page of this document

4

Design for Safety

Figure 4.1 - Safety Block Diagram - Basic ESD and PST

Case A‐B‐C‐D Meaning Action

Monitor Relay
De‐energises?

1

0001

Invalid STOP

Yes

2

0010

CLOSE

No

3

0011

Invalid STOP

Yes

4

0100

CLOSE

No

5

0101

Invalid STOP

Yes

6

0110

Invalid STOP

Yes

7

0111

STOP

No

8

1000

Invalid STOP

Yes

9

1001

OPEN

No

10

1010

Invalid STOP

Yes

11

1011

Invalid STOP

Yes

12

1100

OPEN

No

13

1101

Invalid STOP

Yes

14

1110

Invalid STOP

Yes

15

1111

Invalid STOP

Yes

Case A‐B‐C‐D Meaning Action

Monitor Relay
De‐energises?

1

0001

Invalid STOP

Yes

2

0010

LOCAL

Yes

3

0011

Invalid STOP

Yes

4

0100

LOCAL

Yes

5

0101

Invalid STOP

Yes

6

0110

Invalid STOP

Yes

7

0111

STOP

Yes

8

1000

Invalid STOP

Yes

9

1001 REMOTE

No

10

1010

Invalid STOP

Yes

11

1011

Invalid STOP

Yes

12

1100 REMOTE

No

13

1101

Invalid STOP

Yes

14

1110

Invalid STOP

Yes

15

1111

Invalid STOP

Yes