Limitorque MX Electronic Actuator FCD LMENIM2350-01 – 9/13

flowserve.com

FLOWSERVE PROPRIETARY INFORMATION

Use or disclosure of this information is subject to the restrictions on the title page of this document

5.6 Fail No-Action (Stay Put) Operation

The system is designed so that any single-point failure in the microprocessor-controlled signal lines will automatically
halt or prevent motor motion. We refer to this philosophy as “Fail No-Action.”

While not explicitly considered SIF, this implicit feature would reduce the risk in any SIS that would require the actuator
to stay in place during an emergency.

5.7 Multiple ESD Functions for Basic PST

Up to two independent ESD signals may be applied, prioritized and configured for different actions for the ESD event
associated with each.

ESD Priority 1: Digital Input 0 (Terminal 30)

ESD Priority 2: Digital Input 2 (Terminal 35) Signal is ignored if ESD Priority 1 is asserted.