FCD WCAIM2062-00

Supplement 2: 75 DeviceNet PLC

3

14. In this example, with the scanner located in slot 4 the addresses

of I/O data in the PLC are as follows:

PLC Input Table: 11 bytes of data (output data from the slave)

BYTE-I

1:4.0 (word-O-not used)

1:4.1/0 Bit 0 Actuator Closed CW Switch

1:4.1/1 Bit 1 Actuator Open CCW Switch

1:4.1/2 Bit 2 Not used

1:4.1/3-Bit 3 Actuator CCW Relay (Coil 1) Continuity

1:4.1/4 Bit 4 Actuator CW Relay (Coil 2) Continuity

1:4.1 Bits 5-7 Not used

BYTES-2,3,4,5

1:4.1/Bit 8 to 1:4.3/Bit 7 Maintenance Counter Binary
Format

BYTES-6,7,8,9

1:4.3/Bit 8 to 1:4.5/Bit 7 Cumulative Counter Binary
Format

BYTE-10

Not used

BYTE-11

Not used

PLC Output Table: 1 byte of data (input data to the slave)

0:4.0/0- WORD-0/Bit 0 Establishes the operating mode of
the scanner

Bit 0 =1 Scanner maps I/O from the slaves. This Bit has to
be on for the outputs to be under PLC proqram control.

Bit 0 =0 Scanner stops mapping output data to the slaves.
Input data is still returned from the slaves. Outputs on the
network are not under PLC program control.

a

CAUTION: The PLC/Process Controller logic should never
set bits 5 and 6 on (1) at the same time in output word 1.

These bits control actuator CCW & CW rotation. Damage to
the relay interface module and motors will result if these bits
are set on (1) simultaneously. The output word 1 corresponds
to an actuator at Address 1.

O:4.1/0 Bits 0,1,2,3,4 Not Used

O:4.1/5 Bit 5 CCW Relay (Coil 1) Actuator goes in CCW direction
when =1 and stays in position when =0.

O:4.1/6 Bit 6 CW Relay (Coil 2) Actuator goes in CW direction
when =1 and stays in position when =0.

O:4.1/7 Bit 7 Resets Maintenance counter when =1.