Operation, Worcester controls – Flowserve 10 ACCESS I 39 Actuators User Manual

Page 9

Advertising
background image

WCAIM2027

10, 15, 20 ACCESS I 39 Actuators

9

OPERATION

A. Double-Acting with Control Block – Air is supplied to the

Z\v" NPT

port on the block. When the solenoid is energized, the spring-
loaded plunger is withdrawn, allowing the supply air to shift the
spring-loaded spool within the block, which opens the supply
path to the center chamber of the actuator. Air from the end
chambers of the actuator is allowed to pass through the block
and exhaust to atmosphere.

When the solenoid is de-energized, the spring-loaded plunger
blocks the flow of air to the spool seal within the block and the
spool spring shifts the spool within the block to a position which
opens the supply path to the end chambers of the actuator. Air
from the center chamber of the actuator is allowed to pass
through the block and exhaust to atmosphere.

The actuator is electrically fail-safe. That is, it will return to its de-
energized position upon electrical failure.

The unit has two independently adjustable speed control screws
that can be used to adjust the speed of operation for the opening
and/or closing stroke (see figure 1). If the speed control screws
are too tight, the unit will fail to operate.

NOTE: Speed control screws are shipped from the factory in the
full-open position.

B. Spring-Return with Control Block – Air is supplied to the

Z\v" NPT

port on the block. When the solenoid is energized, the spring-
loaded plunger is withdrawn, allowing the supply air to shift the
spring-loaded spool within the block, which opens the supply
path to the center chamber of the actuator. Air from the end
chambers of the actuator is allowed to pass through the block
and exhaust to atmosphere.

When the solenoid is de-energized, the spring-loaded plunger
blocks the flow of air to the spool within the block and the spring-
loaded spool returns to a position which allows air from the
center chamber of the actuator to pass through the block and
exhaust to atmosphere as the actuator is cycled by the springs in
the end chambers of the actuator. The end chambers are
exhausted to atmosphere at all times.

The actuator is fail-safe. That is, it will return to its de-energized
position upon electrical or pneumatic failure.

The unit has one speed control screw, which can be used to
adjust the speed of operation for the closing stroke (on a fail-
closed unit) or opening stroke on a fail-open unit, and one port
plugged with a red plastic plug (see figure 1). If the speed control
screw is too tight, the unit will fail to operate.

NOTE: Speed control screws are shipped from factory in the full-
open position.

CAUTIONS: If converting a double-acting actuator to a spring-
return actuator or vice-versa, be sure the correct control block
gasket is used. Also, be sure that all gaskets are properly
installed. See figure 2 below and actuator exploded view. Do not
apply any grease to gasket, it must be installed dry. Be sure red
plastic plug is installed in plugged port (see figure 1) for spring-
return actuators.

C. Double-Acting with No Solenoid and No Control Block – Air is

supplied to the

Z\v" NPT port on the air connection block to the

center chamber of the actuator through a remotely mounted four-
way solenoid (or similar supply system). The other

Z\v" NPT port

on the air connection block to the end chambers is exhausted
through solenoid (or similar supply system). When solenoid is
de-energized (energized) supply air is now supplied to end
chambers and center chamber is simultaneously exhausted
through solenoid.

D. Spring-Return with No Solenoid and No Control Block – Air is

supplied to the

Z\v" NPT port on the air connection block to the

center chamber of the actuator through a remotely mounted
solenoid or similar supply system. The other

Z\v" NPT port on the

air connection block is the exhaust port for the end chambers and
may be exhausted to atmosphere or through customer’s system.

When the remotely mounted solenoid or similar supply system
blocks the supply air to the center chamber of the actuator, a
means must be supplied to exhaust this chamber and the actuator
is cycled by the springs in the end chambers.

E. Stroke Times – For stroke times of the Access I Series 39

actuator with solenoid and control block, consult factory. Times
will be measured in seconds and will represent average times
under 50% load conditions with an air supply pressure of 80 psig.
Times will be per stroke for double-acting actuators. For spring-
return actuators, the opening stroke times may be slightly longer;
stroke times for the closing (spring) stroke will be dependent
upon the number of springs used. Cycle times for customer air
supply systems will be dependent upon customer equipment.

F.

Manual Operation – In the event of air failure, the Access I Series
39 actuator can be cycled manually. This is accomplished by
applying a wrench to the exposed top shaft of the actuator and
turning it in the desired direction.

a

WARNING: Care must be taken to ensure that the actuator is

not operated automatically while manual operation is being
performed.

If a routine cycle check is to be performed on an actuator with a
control block, the actuator can be cycled manually by shifting
the spool valve within the control block. This can be done by
pushing the override button in the control block. See figure 1 on
page 8 for location of button. Care must be taken to hold the
spool valve in the desired position until the actuator has cycled.
Provided the air supply is still on, the actuator will cycle to its
original position as soon as the manually applied pressure on
the override button is released.

Flow Control Division

Worcester Controls

Advertising
This manual is related to the following products: