WCAIM2012

Supplement 1 – ACCESS I and M DeviceNet Specification

5

Common Services

Implemented For:

Service Code

Class

Instance

Service Name

14 (0x0E)

Yes

Yes

Get_Attribute_Single

(1) Max Object Instance = 5

(2) Input Value determines overall condition of inputs. The LED

indicators will reflect state of inputs.

State

x

Interpretation

OFF

0

Input is OFF. LED is OFF

ON

1

Input is ON. LED is ON

Discrete Output Point (DOP) Object
Class Code: 09 (0x09)

The Discrete Output Point (DOP) Object models discrete inputs in a
product. You can use this object in applications as simple as a toggle
switch or as complex as a discrete I/O control module. There is a
separate instance for each discrete output available on the device.

DOP Object Class Attributes

Attribute

Access

Name

Type

Value

1

Get

Revision

UINT

1

2

Get

Max Object Instance

UINT

7

6

Get

Max Class Identifier

UINT

7

7

Get

Max Instance Attribute

UINT

8

DOP Object, Instance 1…2 Attributes

Attribute

Access

Name

Type

Value

3

Get/Set

Value

BOOL

(1)

4

Get

Status

BOOL

(1)

5

Get/Set

Fault State

BOOL

(2)

6

Get/Set

Fault Value

BOOL

(2)

7

Get/Set

Idle State

BOOL

(3)

8

Get/Set

Idle State

BOOL

(3)

Common Services

Implemented For:

Service Code

Class

Instance

Service Name

14 (0x0E)

Yes

Yes

Get_Attribute_Single

16 (0x10)

No

Yes

Set_Attribute_Single

(1) Output Value and Status determine overall condition of outputs.

State

x

Interpretation

OFF

0

Output is OFF

ON

1

Output is ON

State

x

Interpretation

OK

0

Output is OK

FAULT

1

Output is at FAULT

(2) The Fault Value and Fault State determine the unit’s reaction to an

output fault condition.

Under normal operation the status information has the same state
as Output value. If a fault condition is detected the status is the
complement of the Output value.

State

x

Interpretation

0

0

Turn output OFF and OK

1

1

Turn output ON and OK

0

1

Turn output OFF and faulted

1

0

Turn output ON and faulted

(3) The Idle Value and Idle State determine the unit’s reaction to an
output idle condition.

State

x

Interpretation

0

0

Turn output OFF if idle

0

1

Turn output ON if idle

1

x

Leave output unchanged if idle

Acknowledge Handler
Class Code: 43 (0x2b)

The Acknowledge Handler is used to manage the reception of
message acknowledgements.

Acknowledge Object, Class Attributes

Attribute

Access

Name

Type

Value

1

Get

Revision

UINT

1

Acknowledge Object, Instance 1 Attribute

Attribute

Access

Name

Type

Value

1

Get/Set

Acknowledge Timer

UINT

(1)

2

Get/Set

Retry Counter

USINT

(2)

3

Get

COS Producing

UINT

4

Connection Instance

Common Services

Implemented For:

Service Code

Class

Instance

Service Name

14 (0x0E)

Yes

Yes

Get_Attribute_Single

16 (0x10)

No

Yes

Set_Attribute_Single

(1) The Acknowledge Timer sets the interval after which new data can

be produced.

(2) Retry counter sets the number of times the COS/Cyclic message is

sent.

Flow Control