Worcester controls – Flowserve Worcester Controls Supplement 1 ACCESS I User Manual

Page 2

Advertising
background image

2

Supplement 1 – ACCESS I and M DeviceNet Specification

WCAIM2012

Implemented For:

Service Code

Class

Instance

Service Name

05 (0x05)

No

Yes

Reset

14 (0x0E)

Yes

Yes

Get_Attribute_Single

(1) Vendor ID is 469
(2) Device Status

bit 0

owned

0=not owned
1=owned (allocated)

bit 1

reserved

0

bit 2

configured

0

bit 3

reserved

0

bit 4-7

vendor specific

0

bit 8

minor cfg. fault

0=no fault
1=minor fault

bit 9

minor device fault

0=no fault
1=minor device fault

bit 10

major cfg. fault

0=no fault
1=major cfg. fault

bit 11

major device fault

0=no fault
1=major device fault

bit 12-15

reserved

0

(3) Unique Serial Number
(4) Present state of the device

value 0

Nonexistent

value 1

Device Self-Testing

value 2

Standby

value 3

Operational

value 4

Major Recoverable Fault

value 5

Major Unrecoverable Fault

Router Object
Class Code: 02 (0x02)

The Message Router Object provides a messaging connection point
through which a Client may address a service to any object class or
instance residing in the physical device.

Router Object Class Attributes

Attribute

Access

Name

Type

Value

1

Get

Revision

UINT

1

6

Get

Max Class Identifier

UINT

7

7

Get

Max Instance Attribute

UINT

2

Router Object, Instance 1 Attributes

Attribute

Access

Name

Type

Value

2

Get

Number of Connections UINT

4

Common Services

Implemented For:

Service Code

Class

Instance

Service Name

14 (0x0E)

Yes

Yes

Get_Attribute_Single

16 (0x10)

No

Yes

Set_Attribute_Single

DeviceNet Object
Class Code: 03 (0x03)

DeviceNet Object Class Attributes

Attribute

Access

Name

Type

Value

1

Get

Revision

UINT

1

Router Object, Instance 1 Attributes

Attribute Access

Name

Type

Value

1

Get/Set

MACID

USINT

(1)

2

Get/Set

Baud Rate

USINT

(2)

3

Get/Set

Bus Off Interrupt

BOOL

(3)

4

Get/Set

Bus Off Counter

USINT

(4)

5

Get/Spc

Allocation Information

STRUCT of (5)

Choice Byte

BYTE

Master Node Address

USINT

6

Get

MAC ID

BOOL

0 = No Change

Switch changed

1= Changed since
last Reset or
Power-up.

7

Get

MAC ID

BOOL

0 = No Change

Switch Value

1= Changed since
last Reset or
Power-up.

8

Get

MAC ID

USINT

Range 0 - 63

Switch Value

9

Get

Baud Rate

USINT

Range 0 - 2

Switch Value

Common Services

Implemented For:

Service Code

Class

Instance

Service Name

14 (0x0E)

Yes

Yes

Get_Attribute_Single

16 (0x10)

No

Yes

Set_Attribute_Single

75 (0x4B)

No

Yes

Allocate Master/Slave

76 (0x4C)

No

Yes

Release Master/Slave

(1) Settable only if switch 7/8 are both in the ON position. Value

returned will be switch 1..6 or last value set. (Attributes 6-8 are
not implemented in this configuration.)

(2) Settable by switch 7/8 or through DeviceNet if switch 7 and 8 are

both on.

Switch/Value

Speed

0

125 kbits

1

250 kbits

2

500 kbits

3

undefined

(3) Bus Off Interrupt (BOI) determines action if Bus Off state

encountered. Following values are supported:

BOI

Action

0

Hold chip in OFF state (default)

1

If possible reset CAN chip

Flow Control

Worcester Controls