Installation

NRG 16-51, NRG 17-51, NRG 19-51, step 1

. Screw electrode tip 4 into measuring electrode 1.

Fig. 7

. Carefully determine required measuring length of electrode.
3. Mark length of electrode tip 4.
4. Unscrew electrode tip 4 from measuring electrode 1 and cut tip.
5. After visual inspection screw electrode tip 4 into measuring electrode 1. Slide spring 3 along

electrode tip 4 so that its end completely enters the small hole 2.

NRG 16-51, NRG 17-51, NRG 19-51, step 2

6. Check seating surfaces.

Fig. 10

7. Place joint ring 5 onto seating surface 6 of the electrode.

Fig. 8

8. Apply a light smear of silicone grease (e. g. WINIX

®

50) to electrode thread 7.

9. Screw level electrode into threads or flange provided on vessel and tighten with a 4 mm

open-end spanner.

The torque required

when cold is 160 Nm.

NRG 16-50F, NRG 17-50F, NRG 19-50, additional information

One level electrode NRG ...-5 F can be installed together with one GESTRA level electrode (with

aluminium terminal box) in a single protection tube or external level pot.

Please proceed as follows:
. Mount level electrode NRG ...-5F as first device as described in items 6 – 9.
When installing level electrode NRG ...-5 F, please observe the following instructions:
. Unscrew screws

g

and remove housing cover

i

.

Fig. 12. The arrow on the name plate points

towards this cover.

. Loosen nut

j

with a 9 mm spanner, but do not remove!

Fig. 13

3. Turn terminal box into desired position (+/– 80°).
The terminal box can now be turned through +/– 180° .
4. Tighten nut

j

with a torque of

25 Nm.

5. Mount housing cover

i

and tighten screws

g

.

Note

n

One level electrode NRG ...-5 can be installed together with one GESTRA water

level limiting electrode in a single protection tube or external level pot (inside diameter

00 mm).

Fig. 16.