Application

Usage for the intended purpose

The level electrodes NRG 6-5, NRG 7-5 and NRG 9-5 are used in conjunction with level switch

NRS -5 as high water level alarms for steam boiler plants and (pressurized) hot water installations.

A high level alarm prevents the water level from exceeding the preset max. water level (HW) and for this

purpose switches off e. g. the feedwater supply.

Function

When the level exceeds the max. water level, the level electrode enters the liquid and an alarm is

triggered in the level switch NRS -5. The switchpoint “High level (HW) exceeded” is dictated by the

length of the electrode rod.
The self-monitoring function ensures that an alarm will also be triggered if the electrode insulation is

contaminated or has developed a leak or if there is a malfunction in the electrical connection.
The level electrode is installed inside steam boilers, vessels or inlet lines of hot-water systems. The

protective tube mounted on site (see section

Examples of Installation (pages 8, 9) ensures correct

functioning.
One level electrode NRG ...-5 can be installed together with one GESTRA water level limiting

electrode in a single protection tube or external level pot.
If the level electrode is installed in a level pot outside the boiler, make sure that the connecting lines

are rinsed regularly. In addition, the logic unit SRL is required to monitor the purging times and the

purging sequence.
If the connecting lines for steam ≥ 40 mm and water ≥ 00 mm, the installation is considered to be

internal. In this case the rinsing processes do not have to be monitored.