Commissioning, Wiring – Flowserve NRG16-12 User Manual

Page 17

Advertising
background image

7

Apply mains voltage to level switch NRS -8.

Commissioning

Check whether the NRG …-2 and the associated controller NRS -8 are wired in accordance with

the wiring diagram.

Fig. 15, Fig. 16

Check wiring

Apply mains voltage

Wiring

– continued –

Tools

Screwdriver for cross-recess head screws, size 

Screwdriver for slotted screws, size 2.5, completely insulated according to DIN VDE 0680-

Open-end spanner A. F. 8 (9)

Voltage table

Use this voltage table as a reference when checking whether the level electrode is submerged or if

there is a malfunction. Please take the wiring diagram of the electrode NRS -8 into account.

Fig. 15, Fig. 16

Note

The self-checking routine of the amplifier NRS -8 reduces

U

-2

every 40 seconds to

0 volt!

U

-2

2 V

eff

C=0.3 cm

-

0 µS/cm

0.5 µS/cm

U

-2

0 V

eff

C=0.3 cm

-