Commissioning, Operation – Flowserve ER 50-1 User Manual

Page 16

Advertising
background image

6

. Check the switching function “High Level Alarm (HW)” of the electrode tip

4 .

For this purpose raise the water level in the vessel above the high water mark. As soon as the water

exceeds the high level mark the level switch must trigger a high level alarm.

. Check the switching functions “Pump ON” and “Pump OFF”,

see table “Functions”.

Commissioning

. Make sure that the system ER 50-/ ER 56- has been wired in accordance with the wiring diagram,

Fig. 11.

. Make sure that the mains supply corresponds to the wiring carried out on the equipment.

Checking electrical connection

Checking the assignment of the switching functions

Operation

ER 50-1, ER 56-1

Operation in conjunction with level switch NRS - for fill and discharge control with first low level

alarm.

Operation in conjunction with NRS -5 for fill and discharge control with high-level alarm.

Operation in conjunction with NRS - as first low-level alarm and high-level alarm in (pressurised) hot

water and steam plants to TRD 40, TRD 60, TRD 604, EN 95, EN 953 or according to national

regulations.

Operation in conjunction with NRS -3 as water level limiter with test button for steam boilers up to

max. 0.5 bar or in feedwater or condensate tanks.

Note

■

Should malfunctions occur during the commissioning procedure refer to chapter

“Troubleshooting” on page 7 in order to analyse and correct them.