Troubleshooting – Flowserve ER 50-1 User Manual

Page 17

Advertising
background image

7

Troubleshooting

Fault finding list

Level has exceeded switchpoint “High Water” – no function

Fault:

Mains voltage has not been applied.

Remedy: Apply mains voltage. Wire equipment according to the wiring diagram.

Fault:

The electric conductivity is too low.

Remedy: Use level switch with higher response sensitivity (0.5 μS/cm).

Fault:

The electrode body does not have earth connection to the boiler.

Remedy: Clean seating surfaces and insert metal joint ring (of stainless steel .430) to 33 x 39 to

DIN 7603. Do not insulate compact system with hemp or PTFE tape!

Level has fallen below switchpoint “Low Water” – no function

Fault:

The electrode tips have earth connection.

Remedy: Change installation position.

Fault:

The vent hole in the protection tube does not exist, is obstructed or flooded.

Remedy: Check protection tube and, if necessary, provide vent hole.

Fault:

The isolating valves of the external measuring pot (optional) are closed.

Remedy: Open isolating valves.

Switchpoint has been reached – incorrect function

Fault:

The switching function has not been correctly allocated. Electrode tips have been cut to the

wrong length.

Remedy: Identify electrode supply wire and reconnect accordingly.

If faults occur that are not listed above or cannot be corrected, please contact our service centre or

authorized agency in your country.

Advertising
This manual is related to the following products: