Troubleshooting

Fault finding list

Level has exceeded switchpoint “High Water” – no function

Fault:

Mains voltage has not been applied.

Remedy: Apply mains voltage. Wire equipment according to the wiring diagram.

Fault:

The thermal fuse has been triggered.

Remedy: In case of defective thermal fuse the mains voltage has not been connected to terminal

L:

Replace defective thermal fuse (Order No. 05629)

The ambient temperature must not exceed 70 °C.

Fault:

The electric conductivity is too low.

Remedy: Set code switch

4 to ≥ 0.5 µS/cm.

Fault:

The electrode housing does not have earth connection to the boiler.

Remedy: Clean seating surfaces and insert metal joint ring (of stainless steel .430) 33 x 39 to

DIN 7603. Do not insulate compact system with hemp or PTFE tape!

Fault:

Electronic board is defective.

Remedy: Replace board, Order No. 39556 (5/230 V a.c.), 39636 (24 V a.c.).

Level has fallen below switchpoint “Low Water” – no function

Fault:

The electrode tips have earth contact.

Remedy: Change installation position.
Fault:

The vent hole in the protection tube does not exist, is obstructed or flooded.

Remedy: Check protection tube and, if necessary, provide vent hole.

Fault:

The isolating valves of the external measuring pot (optional extra) are closed.

Remedy: Open isolating valves.

Switchpoint has been reached – incorrect function

Fault:

The switching function has not been correctly allocated. Electrode tips have been cut to

the wrong size.

Remedy: Identify electrode supply wire and reconnect accordingly.

If faults occour that are not listed above, please contact our subsidiary or agency in your country.