Wiring, Connecting the measuring element, Fig. 10 – Flowserve TRG 5-6x User Manual

Page 14

Advertising
background image

14

Wiring

TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68

Use screened four-core cable for wiring, e. g. Ölflex 110 CH, produced by Lapp, 4 x0.5 mm². Max. cable
length between temperature sensor and temperature transmitter TRV 5-40: 25 m.

Connecting the measuring element

1. Take cover

off the terminal box

.

2. Unscrew dome nut

of the cable gland

and take out the lamellar insert

Fig.10.

3. Cut off outer cable sheath

and expose braided screen

over a length of approx. 10-15 mm.

4. Push dome nut

and lamellar insert

with sealing ring

onto the cable

.

5. Bend braided screen

outwards at a right angle (90°).

6. Fold braided screen

towards outer sheath, i. e. by another 180°.

7. Push lamellar insert

with sealing ring

into gland body

and turn it briefly around both sides of

the cable axis and snap anti-rotation element into place.

8. Firmly screw on dome nut

.

9. Connect the connecting cable in accordance with the wiring diagram to the measuring element

.

10.Replace cover

and tighten screw securely.