Commissioning

Chec k wiring

Check that the temperature sensor TRG 5-6x and its associated temperature transmitter TRV 5-40 have
been wired in accordance with the wiring diagram (see page 15).

Apply mains voltage

1. Apply mains voltage or bus supply voltage to the control unit NRS 1-40.1.

Me asure fluid temperature

Use the following table to ascertain the current temperature of the fluid, using the resistance value of the
Pt 100.

1. Take cover

off the terminal box.

2. Connect test cable directly to the measuring element

.

3. Use an ohmmeter for measuring the resistance value.

4. Look up the corresponding resistance value in the table, interpolate if necessary and read off the tem-

perature.

5. Replace cover

and tighten screw securely.

Basic values of the precision resistors according to DIN 43760 for Pt 100.

Tools

Screwdriver for slotted screws, size 2.5, completely insulated according to DIN VDE 0680-1

Screwdriver for slotted screws, size 8

°C

0

10

20

30

40

50

60

70

80

90

100

:

/deg

0

100.00 103.90 107.79 111.67 115.54 119.40 123.24 127.07 130.89 134.70 138.50

0.385

100

138.50 142.28 146.06 149.82 153.57 157.32 161.04 164.76 168.47 172.16 175.84

0.373

200

175.84 179.51 183.17 186.82 190.46 194.08 197.70 201.30 204.88 208.46 212.03

0.361

300

212.03 215.58 219.13 222.66 226.18 229.69 233.19 236.67 240.15 243.61 247.06

0.350

400

247.06 250.50 253.93 257.34 260.75 264.14 267.52 270.89 274.25 277.60 280.93

0.338

500

280.93 284.26 287.57 290.87 294.16 297.43 300.70 303.95 307.20 310.43 313.65

0.327

600

313.65 316.86 320.05 323.24 326.41 329.57 332.72 335.86 338.99 342.10 345.21

0.315

700

345.21 348.30 351.38 354.45 357.51 360.55 363.59 366.61 369.62 372.62 375.61

0.304

800

375.61 378.59 381.55 384.50 387.45 390.38

0.295