Annex – Flowserve NRGS 16-2 User Manual

Page 15

Advertising
background image

15

Annex

Warning

The terminal strip of the NRGS 16-2 is live during operation.
This presents the danger of electric shock.
Cut off power supply before removing or replacing housing cover.

Fault finding list

Switchpoint “Pump ON” has been exceeded – no function
Fault:

Mains voltage has not been applied.

Remedy: Apply mains voltage. Wire equipment according to the wiring diagram.

Fault:

The thermal fuse has failed.

Remedy: In case of defective thermal fuse the mains voltage has not been

connected to terminal : Replace defective thermal fuse
(Order No. 051629).
The ambient temperature must not exceed 70 °C.

Switchpoint “Pump OFF” has been exceeded – no function
Fault:

The electric conductivity is too low.

Remedy: Switch DIP switch to

0.5 µS/cm.

Fault:

The electrode housing does not have earth connection to the boiler.

Remedy: Clean seating surfaces and insert metal joint ring (of stainless steel 1.4301)

33 x 39 to DIN 7603.
Do not insulate compact system with hemp or PTFE tape!

Fault:

Electronic board is defective.

Remedy: Replace board (Order No. 391423).

Level has fallen below switchpoint “Low water” – no function

Fault:

The electrode rods have earth contact.

Remedy: Change installation position.

Fault:

The vent hole in the protection tube does not exist, is obstructed or flooded.

Remedy: Check protection tube and, if necessary, provide vent hole.

Fault:

The isolating valves of the external measuring pot (optional) are closed.

Remedy: Open isolating valves.

Switchpoint has been reached – incorrect function

Fault:

The switching function has not been correctly allocated. Electrode rods

have been cut to the wrong size.

Remedy: Identify electrode supply wire and reconnect accordingly.