Flowserve NRGS 16-2 User Manual

Page 9

Advertising
background image

9

Technical Data

Type Approval N°
TÜV

.

WR/WB

.

97-392

Max. service pressure
32 bar g at 238 °C

Connections
Screwed 1" BSP, DIN ISO 228
Flanged DN 50, PN 40, DIN 2635

Materials
Case

Die cast aluminium 3.2161 (G AlSi8Cu3)

Stem

S. S. 1.4571 (CrNiMoTi 17 12 2)

Flange

Forged steel 1.0460 (C 22.8)

Measuring electrodes

S. S. 1.4571 (CrNiMoTi 17 12 2)

Electrode insulation

PTFE

Spacer disc

PTFE

Lengths supplied

1

500 mm

1000 mm
1500 mm

Mains supply
230 V +/– 10 %, 50/60 Hz
115 V +/– 10 %, 50/60 Hz

2

24 V +/– 10 %, 50/60 Hz (option)

Power consumption
5 VA

Fuse
Thermal fuse T

max

= 102 °C

Sensitivity
Range 1: 10

µ S/cm

Range 2: 0.5

µ S/cm

Electrode voltage
10 V

ss

Output
2 volt-free relay contacts. 1 volt-free normally open contact.
Max. contact rating with a switchting voltage of 24 V, 115 V and 230 V a. c.: ohmic 4 A,
inductive 0.75 A at cos

ϕ

0.5. Max contact rating with a switching voltage of 24 V d. c.: 4 A

Contact material: silver, hard-gold plated