background image

105443-01E

For more information, visit www.desatech.com

For more information, visit www.desatech.com

12

4.

A licensed electrician must follow the wiring diagram in Fig-
ure 18 to connect incoming electrical supply to fan kit wiring
harness.

5.

Test to make sure the blower is working properly.

6.

Reinstall hood assembly (see page 9) and close lower louver door.

7.

Place log set back on the unit.

INSTALLATION

Continued

INSTALLATION

Installing Blower Assembly - GA3450T (Cont.)
Connecting To Gas Supply

Figure 18 - Wiring Diagram For Fan Accessory Built-In Installation

If any of the original wire as supplied with the appliance must be
replaced, original replacements must be used. DESA part no.
104015-01 (105°C) for power cord, and DESA part no. 103968-
01 (200°C) for wire harness.

101584-06

120 Vac. 60 Hz. .30 Amps
DESA International, Bowling Green, KY

Red

Red

Fan Switch

(Auto/Off/On)

Blue

Blue

Thermostat

Switch

(N.O.)

Green

White

Green

White

On

110/115

V.A.C.

Blower

Motor

Black

Off

1

2

3

Auto

WARNING: Never attempt to service heater while it is

plugged in, operating, or hot. Burns and electrical shock
could result. Only a qualified service person should ser-
vice or repair heater.

WARNING: Label all wires prior to disconnection

when servicing controls. Wiring errors can cause im-
proper and dangerous operation. Verify proper opera-
tion after servicing.

CONNECTING TO GAS SUPPLY

WARNING: A qualified service person must con-

nect fireplace to gas supply. Follow all local codes.

CAUTION: Never connect fireplace directly to the

propane/LP supply. This fireplace requires an exter-
nal regulator (not supplied). Install the external regu-
lator between the fireplace and propane/LP supply.

CAUTION: Use only new, black iron or steel pipe.

Internally-tinned copper tubing may be used in certain
areas. Check your local codes. Use pipe of 1/2" or greater
diameter to allow proper gas volume to fireplace. If pipe
is too small, undue loss of volume will occur.

Installation Items

Before installing fireplace, make sure you have the items listed below.

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• equipment shutoff valve *

• ground joint union

• sediment trap

• tee joint

• pipe wrench

• test gauge connection*

* A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase
the optional CSA design-certified equipment shutoff valve from
your dealer. See Accessories, page 31.

IMPORTANT:

Check gas line pressure before connecting fireplace

to gas line. Gas line pressure must be no greater than 14 inches of
water. If gas line pressure is higher, fireplace regulator damage
could occur.

Installation must include an equipment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from fireplace (see Figure 19,
page 13).

IMPORTANT:

Install equipment shutoff valve in an accessible

location. The equipment shutoff valve is for turning on or shutting
off the gas to the appliance.

Check your building codes for any special requirements for locating
equipment shutoff valve to fireplaces.