- 14 -

5.2

Controller Display / Menu Structure

To access the user menu press and hold the Units/Menu Select button until “HL” appears. Press and release the
Units/Menu Select button to scroll through the menu items.

Menu Item

Description

Choices / Ranges / Comments

Default
Setting

HL

High Temperature Limit

Alarm Set Point

-15° to 45°C ( 5° to 113°F)

35ºC (95

°F)

LL

Low Temperature Limit
Alarm Set Point

-20°C to +27°C / -4° to 80°F

4ºC (39°F)

HA

Front Panel High
Ambient Temperature
Alarm Set Point

+30° to 75°C. Always displayed and set in °C.

45ºC

FP

w/PSI LED lit

Maximum Fluid
Pressure Alarm Set
Point

10 to 250 PSI

250 PSI

FP

w/KPa LED lit

Maximum Fluid
Pressure Alarm Set
Point

0.68 to 17 (x 100) kPa

17

(x 100) kPa

FL

w/GPM LED lit

Minimum Flow Rate
Alarm Set Point

NA

0.0 GPM

FL

w/LPM LED lit

Minimum Flow Rate
Alarm Set Point

NA

0.0 LPM

Lb

Lower Temperature
Band

1.0 to 5.0

°C.

Always displayed and set in °C

5.0

°C

Ub

Upper Temperature
Band

1.0 to 5.0

°C.

Always displayed and set in °C

5.0

°C

c1

Calibration Offset Temp
1

±2.9°C. Always displayed and set in °C.
Special access procedure required.
See Section 5.13.

0.0

°C

c2

Calibration Offset Temp
2

NA

0.0

°C

c3

Calibration Offset Temp
3

NA

0.0

°C

Cd

Compressor Delay

10 – 300 seconds

20 sec.

Fc

Flow Calibration

NA

Factory Set

dS

Coolant Density

NA

8.35

Sh

Coolant Specific Heat

NA

1.00

PC

Communications Baud
Rate

NA 9600

LA

Low Ambient Alarm
Setpoint

1 to 7

°C. Always displayed and set in °C

2

°C

Pd

Password

0 to 999 (for service use only)

0

td

HGB Valve Delay

0 to 999 (for service use only)

2

NOTE: See Section 5.14 for Alarm and Error messages.