Installation, Continued, Minimum clearance to combustible materials – Desa VMH10TNC User Manual

Page 11: Built-in fireplace installation

Advertising
background image

www.desatech.com

112462-01B

11

Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabi-

net to any combustible material and wall
should follow diagram in Figure 6.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and pro-
trudes 3

1

/2" from the wall. This combustible

material must be 4" from the side of the fire-
place opening (see Figure 6).

B. Clearances from the top of the fireplace

opening to the ceiling should not be less than
36 inches.

C. For mantel clearances, see Figure 10 on

page 12.

Figure 6 - Minimum Clearance for

Combustible to Wall

*Minimum 16 inches from Side Wall

*

Example

MINIMUM CLEARANCE TO

COMBUSTIBLE MATERIALS

Top

Left and

Bottom

Right Sides

and Rear

36"

6"

0"

INSTALLATION

Continued

Actual

Framing

Height

26"

26

7

/

8

"

Front Width

26

3

/

4

"

26

7

/

8

"

Depth

9

1

/

2

"

10

1

/

2

"

Bottom

3/4"

3/4"

1. Frame in rough opening. Use dimensions shown

in Figure 7 for the rough opening. If installing
in a corner, use dimensions shown in Figure 8
for the rough opening. The height is 26

7

/

8

" which

is the same as the wall opening above.

2. If installing GA3450T blower accessory, do

so at this time. Follow instructions included
with blower accessory.
Note:

If not installing blower accessory, you

may wish to run electrical wiring to your fire-
place for future blower installation (see Ac-
cessories,
page 40). Use only approved three-
wire electrical wiring.

WARNING: If pre-wiring, do

not connect wiring to any elec-
trical source at this time.
Install fireplace electrical outlet
and connect wiring to outlet be-
fore connecting to electrical
source. The fireplace electrical
outlet is included with the
GA3450T blower accessory.
Only use the fireplace electrical
outlet supplied with the
GA3450T blower accessory.

Note:

A qualified installer should make all elec-

trical connections.

BUILT-IN FIREPLACE
INSTALLATION

Built-in installation of this fireplace involves in-
stalling fireplace into a framed-in enclosure. This
makes the front of fireplace flush with wall. An
optional trim kit accessory is available (see Ac-
cessories
, page 40). Trim will extend past sides of
fireplace approximately 1/2 inch. This will cover
the rough edges of the wall opening. If installing
a built-in mantel above the fireplace, you must
follow the clearances shown in Figure 10, page
11. Follow the instructions below to install the fire-
place in this manner.

26

7

/

8

"

26

7

/

8

"

3/4" Off
The Floor
Minimum

10

1

/

2

"

Figure 8 - Rough Opening for Installing

in Corner

Figure 7 - Rough Opening for Installing

in Wall

36

5

/

8

"

25

7

/

8

"

51

3

/

4

"

26

7

/

8

"